OTHERS ARE CALCULATED VALUES BASED ON THE BATTERY MANUFACTURER'S DATA FOR BACK UP
TIME.

APPENDIX B – Optional Main Input & Main Output Breakers

for various models (*All Values are typical as reference only)

TABLE B-1: External Output Breaker (Standard KAIC)

Output Voltages

KVA

120 Vac

240 /120 VAC

3

40 Amps, 120 VAC,

1 Pole, 14 KAIC

OLP P/N: 2025-783

20 Amps, 240 VAC,

2 Pole, 10 KAIC

OLP P/N: 2025-788

5

70 Amps, 120 VAC,

1 Pole, 14 KAIC

OLP P/N: 2025-997

40 Amps, 240 VAC,

2 Pole, 10 KAIC

OLP P/N: 2025-791

7.5

100 Amps, 120 VAC,

2 Pole, 10 KAIC

OLP P/N: 2025-999

50 Amps, 240 VAC,

2 Pole, 10 KAIC

OLP P/N: 2025-792

10

125 Amps, 120 VAC,

2 Pole, 10 KAIC

OLP P/N: 2025-759

70 Amps, 240 VAC,

2 Pole, 10 KAIC

OLP P/N: 2025-794

12.5

1750 Amps, 120 VAC,

2 Pole, 10 KAIC

OLP P/N: 2025-468

80 Amps, 240 VAC,

2 Pole, 10 KAIC

OLP P/N: 2025-795

15

200 Amps, 120 VAC,

2 Pole, 65 KAIC

OLP P/N: 2025-541

100 Amps, 240 VAC,

2 Pole, 10 KAIC

OLP P/N: 2025-797

TABLE B-2: Output Breaker (High KAIC)

Output Voltages

KVA

120 Vac

240 Vac

3

40 Amps, 120 VAC,

1 Pole, 42 KAIC

OLP P/N: 2025-799

20 Amps, 240 VAC,

2 Pole, 65 KAIC

OLP P/N: 2025-762

5

70 Amps, 120 VAC,

1 Pole, 42 KAIC

OLP P/N: 2025-998

40 Amps, 240 VAC,

2 Pole, 65 KAIC

OLP P/N: 2025-766

7.5

100 Amps, 120 VAC,

2 Pole, 42 KAIC

OLP P/N: 2025-803

50 Amps, 240 VAC,

2 Pole, 65 KAIC

OLP P/N: 2025-767

10

125 Amps, 120 VAC,

2 Pole, 65 KAIC

OLP P/N: 2025-759

70 Amps, 240 VAC,

2 Pole, 65 KAIC

OLP P/N: 2025-769

12.5

1750 Amps, 120 VAC,

2 Pole, 65 KAIC

OLP P/N: 2025-468

80 Amps, 240 VAC,

2 Pole, 65 KAIC

OLP P/N: 2025-770

15

200 Amps, 120 VAC,

2 Pole, 65 KAIC

OLP P/N: 2025-541

100 Amps, 240 VAC,

2 Pole, 65 KAIC

OLP P/N: 2025-894