OnLine Power

(6002-1646) REV.X8

19

6. At this point in time, the Fire Alarm Back-up UPS1481 should be providing AC line power.

The Fire Alarm Back-up UPS1481 is not operating in the normal mode, turn off the input
circuit breaker. Contact OnLine Power at (800) 797-7782 for technical assistance.

7.

Recheck that the output voltage is 120/240 VAC.

• If the output voltage is approximately same as nameplate, turn on the loads which will

be powered from
the Fire Alarm Back-up UPS1481 .


8.

The next steps verify battery operation and the inverter test switch.


• To place the Fire Alarm Back-up UPS1481 in battery operation (to simulate loss of

input power), press and hold yellow Inverter Test Switch. With switch in the hold
position, the Fire Alarm Back-up UPS1481 should be running on its internal batteries.


• Verify that the LCD panel displays such.

• Verify that the “Battery Charger” is OFF in LCD panel.

Note: Be sure to release the switch, after the test, so it will not deplete the batteries.

9.

The Fire Alarm Back-up UPS1481 is now fully functional - providing clean, sine wave
power to the load with battery back—up in case of an input power failure. This concludes
the start-up procedures.



3-2 Operation

3-2-1 Turning On the Fire Alarm Back-up UPS1481 :

1.

Apply input power.


2.

With input power available, turn on the main input circuit breaker, CB2 (if provided).


3.

Close battery breaker (CB1), only after the LCD display is lit & displays screens per
Appendix D.


4.

Wait till you hear the input contactor closing and fan running.


5.

Verify that all parameters on LCD display panel are proper. See Appendix D for display
details.


6.

Close the output circuit breaker, CB2 (if provided).


7. Turn

load

breakers

On.