APPENDIX D: SPECIFICATION

POWER RATING (KW)

3.0

5.0

7.5

10

12.5

15

VOLTAGE

(VAC) INPUT

Single Phase,

120/208/240

Single Phase, 240/208VAC

MAXIMUM CURRENT

40/19/16

58/30/28

41/36

58/50

69/60

83/72

TOLERANCE

+10% to -15%

FREQUENCY (Hz)

60 +/- 3%

POWER FACTOR

0.98 to 1.0 (Typical)

OVERCURRENT PROTECTION

Electronic / Circuit Breaker

NUMBER OF WIRES

2 Wires plus Ground

POWER CONNECTION

Hard Wired (Terminal Block)

OUTPUT

RATING (KVA/KW)

3.0

5.0

7.5

10

12.5

15

VOLTAGE (VAC)

120/120/240 120/120/240 120/240 120/240 120/240 120/240

VOLTAGE REGULATION

+/-3% No Load to Full Load; +/-3% High Line to Low Line

FREQUENCY (Hz)

60 Hz +/-0.25 Hz (When on Inverter)

WAVESHAPE

Sine Wave

HARMONIC DISTORTION

<5% THD; <3% Single Harmonic

CREST FACTOR

Up to 3 to 1

POWER FACTOR

1.0PF

STEADY-STATE CURRENT

25/12.5

42/20.8

62.5/31.3

83.3/41.7

104/52

125/62.5

OVERLOAD

125 % for One (1) minutes, surge 150 %

PROTECTION

Electronic / Circuit Breaker

NOISE REJECTION

-120 kB Common Mode; -60 kB Normal Mode

NUMBER OF WIRES

2 Wires plus Ground

POWER CONNECTION

Hard Wired (Terminal Block)