Online power – IBM Fire Alarm Back-up UPS1481 UNIT User Manual

Page 39

Advertising
background image

OnLine Power

(6002-1646) REV.X8

33

POWER RATING (KVA/KW)

3.0

5.0

7.5

10

12.5

15

BATTERY

BATTERY RUN TIME

See Appendix C for various Run time

BATTERY TYPE

Sealed, Maintenance-Free, AGM, VRLA type

NOMINAL DC VOLTAGE

96 VDC

120 VDC

120 VDC

192 VDC

192 VDC

240 VDC

OVERCURRENT PROTECTION

Circuit Breaker

PACKAGING

Batteries Housed in Same Enclosure and/or additional battery cabinet (See Table 2-1)

MONITORING AND COMMUNICATIONS

LCD SCREEN

Input Voltage, Batt. Charger, UPS Output; On Batt.; Low Batt.; Summary Alarm

INDICATORS

LCD Display Panel

RELAY INTERFACE

Dry Contacts for:

UPS On (N.C.); On Inverter (N.O.); Loss of Input Power (N.O.); Low Battery (N.O.)

CONTACT RATING

125 Volts (AC or DC) Maximum; 1.25 Amperes Maximum; 30 Watts / 50 VA Maximum

INTERFACE CONNECTION

Hard Wired (Terminal Block)

ENVIRONMENTAL

USRGE WITHSTANDABILITY

ANSI C62.41-1980 Categories A & B

OPERATING TEMPERATURE

Meets NEMA Requirements

OPERATING RELATIVE HUMIDITY

0 to 95% Non-Condensing

ALTITUDE

Up to 6,000 Feet (1,829 Meters) with No De-Rating

COOLING

Air Cooled-Forced Fan

PHYSICAL

SIZE WxHxD in. (cm)

18 x 35 x 32 (45.7 x 88.9 x 84.3 cm)

WEIGHT ibs (kg) with batteries

600(273)

900(409)

1150(523)

1600(727)

1850(841)

2250(1023)

CONSTRUCTION

Painted Steel Enclosure with 3 Point Double Locking Front Door; and Full-Length Door Hinge.

ENCLOSURE

Designed for Inside Installations

COLOR

Natural finish

ACCESSIBILITY

Front - All Servicing is Through the Front; No Side or Rear Access is Required.

CABLE ENTRY

Bottom or sides

MOUNTING

Four (4) Holes Provided to Anchor Enclosure to Pedestal (Supplied by Others)