Ole_link3, Ole_link4 – ICP DAS USA RS-405/405F User Manual

Page 27

Advertising
background image

Industrial Redundant Ring Switch

– RS Series User Manual

TDRS4050601

t

Time Status

Upper right section displays Time Status. You can monitor and configure current Time

setting interval in this section: Recovery Time(in the range 100-65535ms), Max Age

Time(in the range 6000-40000ms), Forward Delay(in the range 4000-30000ms), and

Hello Time (in the range 1000-10000ms). To make a modification, please type new
values in the fields that you would like to make a change of, and then click on the

button. Please note: the

button will appear

( gray out) before you input new

values. To make the value you input effectively, please click on

“Restart” button.

Note that the Switch Value indicates the value you configure and save on this Ring
Switch. However, only the Switch Value being set on Master Switch will be adapt as the

actual value (Operating Value) being applied to all switches in the same ring.

DIP Switch Status

This section shows current DIP Switch Status. Each jumper has two possible conditions:
on or off. Each position indicates one configuration state. To make a change of the

jumper state, please switch the jumpers on the Ring Switch directly and then click
“Restart” button to make the newly changed settings effective.

Advertising
This manual is related to the following products: