Industrial Redundant Ring Switch

– RS Series User Manual

TDRS4050601

iii

Event Type 1: Power 1 Error

• Check for faulty power cord.

• Check for loose or broken power connections.

• Check connections to ensure the power and ground are attached to the correct terminals.

• Check for power loss or power surges at the AC power outlet.

• Check Voltage of power coming into Power 1 to ensure it is within +10 - +30V DC.

• Ensure there are no shorts between power and ground.

If the above fails, contact support.

Event Type 2: Power 2 Error

• Check for faulty power cord.

• Check for loose or broken power connections.

• Check connections to ensure the power and ground are attached to the correct terminals.

• Check for power loss or power surges at the AC power outlet.

• Check Voltage of power coming into Power 2 to ensure it is within +10 - +30V DC.

• Ensure there are no shorts between power and ground.

If the above fails, contact support.

Event Type 3: RS-232/RS-485 Connection Error

• Check for faulty cable line.

• Check for loose or broken connections.

If the above fails, contact support.

Event Type 4: Link Error

• Check if the corresponding DIP Switch (SW1) is “on”.

• Check for faulty or loose Cables(both ends). Visually inspect for loose or faulty connections at all
connectors and cables. If that does not correct the problem, try replacing the cable.