Replacing a fan module, Replacing a redundant fan module, Remove the optical drive cable if installed – Intel SERVER SYSTEM SR2500AL User Manual

Page 113: Disconnect the fan cables from the mid-plane, R instructions, see, For instructions, see

Advertising
background image

Intel® Server System SR2500AL User’s Guide

91

8. Install the server system cover. For instructions, see

“Installing the Server System

Cover”

.

9. (Optional) Install the front bezel. For instructions, see

“Installing the Front Bezel”

.

10. Plug all peripheral devices and the AC power cable(s) into the server.

Replacing a Fan Module

Replacing a Redundant Fan Module

1. Observe the safety and ESD precautions at the beginning of this book. See

“Safety

Information”

.

2. Power down the server and unplug all peripheral devices and the AC power

cable(s).

3. Remove the server system cover. For instructions, see

“Removing the System

Cover”

.

4. Remove the processor air duct. For instructions, see

“Removing the Processor Air

Duct”

.

5. Remove the PCI riser assembly. For instructions, see

“Removing the PCI Riser

Assembly”

.

6. Remove the optical drive cable if installed.
7. Remove the bridge board. For instructions, see

Figure 61 “Removing the Bridge

Board from the Server System” on page -71

.

8. Remove the large air baffle. For instructions, see

“Removing the Large Air Baffle”

.

9. Disconnect the fan cables from the mid-plane.