Installing a fan tray in an ex8208 switch – Juniper Networks EX8208 User Manual

Page 180

Advertising
background image

Figure 53: Installing a DC Power Supply in an EX8200 Switch

Related Topics

Removing a DC Power Supply from an EX8200 Switch on page 209

DC Power Supply in an EX8200 Switch on page 48

Installing a Fan Tray in an EX8208 Switch

An EX8208 switch has a single, field-replaceable fan tray. The fan tray is a hot-insertable
and hot-removable field-replaceable unit (FRU); you can remove and replace the fan
tray while the switch is running without turning off power to the switch or disrupting
switching functions.

The fan tray installs vertically on the left side on the front of the chassis. A handle on the
front faceplate facilitates handling of the fan tray. There is a spring-loaded latch on the
base of the fan tray that is used to latch the fan tray into the chassis.

Before you begin to install a fan tray:

Ensure you understand how to prevent ESD damage. See “Prevention of Electrostatic
Discharge Damage on EX Series Switches” on page 292
.

Ensure that you have the following parts and tools available to install a fan tray in an
EX8208 switch:

Electrostatic discharge (ESD) grounding strap

CAUTION: The fan tray can be removed and replaced while the switch is operating.
However, the fan tray must be replaced within 2 minutes of removing the fan tray to
prevent the chassis from overheating.

To install a fan tray in an EX8208 switch (see Figure 54 on page 155):