Johnson Controls XP-910x User Manual

Page 11

Advertising
background image

Configuration Guides—XT-9100 Configuration Guide 11

Via the SX Tool

The input type for the eight possible inputs (n = 1 to 8) can be configured
in Item AITn (RI.88, RI.96, RI.104, RI.112, RI.120, RI.128, RI.136, and
RI.144).

The unit of each analog input can be selected with following bits: (For
RTD inputs, Celsius or Fahrenheit must be selected.)

X4 X3 X2 X1 = 0000

No Units

X4 X3 X2 X1 = 0001

Celsius

X4 X3 X2 X1 = 0010

Fahrenheit

X4 X3 X2 X1 = 0011

Percent

Changing individual temperature units for each AI can only be done in the
SX Tool.

This function allows the linearization of the differential pressure signal
from a 0-10 VDC or 0/4 - 20 mA active sensor; the function is effective
over the selected range:

AI = sqrt(PR%/100) * (HR - LR) + LR

Where %PR = the Analog Value in % of the physical input range;
HR = High Range Value; and LR = Low Range Value.

Via the GX Tool (Option Only Available with Active Sensor)

Select XTn, AIn, and Data. At the “Square Root” field, enter “0” for No,
or “1” for Yes (to enable the square root calculation).

Via the SX Tool (Option Only Available with Active Sensor)

Select Item AITn.

X5 = 1

Enable Square Root of Input

X5 = 0

Disable Square Root of Input

AI Input Type:
Enable Square
Root