Johnson Controls XP-910x User Manual

Page 34

Advertising
background image

34 Configuration Guides—XT-9100 Configuration Guide

RI.

HI.

Type

R/W

Tag

Description

79

4F

1 Byte

CNF

IOMOD

Extension Module I/O Mode

X8 X7 X6 X5 X4 X3 X2 X1

X1 = 0

XP1

: I/O1 and I/O2 Input

X1 = 1

XP1

: I/O1 and I/O2 Output

X2 = 0

XP1

: I/03 and I/O4 Input

X2 = 1

XP1

: I/O3 and I/O4 Output

X3 = 0

XP1

: I/O5 and I/O6 Input

X3 = 1

XP1

: I/O5 and I/O6 Output

X4 = 0

XP1

: I/O7 and I/O8 Input

X4 = 1

XP1

: I/O7 and I/O8 Output

X5 = 0

XP2

: I/O1 and I/O2 Input

X5 = 1

XP2

: I/O1 and I/O2 Output

X6 = 0

XP2

: I/O3 and I/O4 Input

X6 = 1

XP2

: I/O3 and I/04 Output

X7 = 0

XP2

: I/O5 and I/O6 Input

X7 = 1

XP2

: I/O5 and I/O6 Output

X8 = 0

XP2

: I/O7 and I/O8 Input

X8 = 1

XP2

: I/O7 and I/O8 Output

80

50

1 Byte

CNF

Spare

81

51

1 Byte

CNF

Spare

82

52

1 Byte

CNF

Spare

83

53

1 Byte

CNF

Spare

84

54

1 Byte

CNF

Spare

85

55

1 Byte

CNF

Spare

86

56

2 Byte

CNF

MTBC

Maximum Time Between

Communications (default = 60 sec.)

87

57

2 Byte

CNF

AOT

Analog Output Type

X16 X15 X14 X13 X12 X11 X10 X9

X8 X7 X6 X5 X4 X3 X2 X1

X2 X1

Signal Analog Output 1

= 00

Output Disabled

= 01

Output 0 to 10V

= 10

Output 0 to 20 mA

= 11

Output 4 to 20 mA

X4 X3

Signal Analog Output 2 (as X2 X1)

X6 X5

Signal Analog Output 3 (as X2 X1)

X8 X7

Signal Analog Output 4 (as X2 X1)

X10 X9

Signal Analog Output 5 (as X2 X1)

X12 X11

Signal Analog Output 6 (as X2 X1)

X14 X13

Signal Analog Output 7 (as X2 X1)

X16 X15

Signal Analog Output 8 (as X2 X1)

Advertising
This manual is related to the following products: