22 Configuration Guides—XT-9100 Configuration Guide

Upload via a DX-9100 Controller

Only complete DX-9100/XT-9100 configurations should be uploaded
from the DX-9100. Select DX-9100 and NEW to clear the PC screen.
Select DX-9100, UPLOAD, and DX&XT. Enter the DX-9100 Controller
address (0-255) and PC port (1 or 2). Press <Enter>.

Download via the N2 Bus

Set the address switches and jumpers on the XT/XP devices as required.
Connect the XT/XP devices to the N2 Bus and the N2 Bus to the converter
on the PC. (See the XT-9100 Technical Bulletin (LIT-6364040) for
connection details.)

If the XT/XP devices are installed and wired, verify all field wiring and
sensor voltage/current signals. It is recommended that controlled devices
be isolated during download and initial startup. Apply 24 VAC power to
the XT/XP devices.

Up to eight XT-9100s may be downloaded at one time from the GX Tool
over the N2 Bus.

If the XT/XP devices are not used with a DX-9100, it is recommended that
one configuration file is created for each XT-9100 in Position XT1.

Set the address switches and jumpers on the XT/XP devices as required.
Connect the XT/XP devices to the N2 Bus and the N2 Bus to the converter
on the PC. (See the XT-9100 Technical Bulletin (LIT-6364040) for details.)

If the XT/XP devices are installed and wired, verify all field wiring and
sensor voltage/current signals. It is recommended that controlled devices
be isolated during download and initial startup. Apply 24 VAC power to
the XT/XP devices.

Up to eight XT-9100s may be downloaded at one time from the GX Tool
over the N2 Bus.

If the XT/XP devices are not used with a DX-9100, it is recommended that
one configuration file is created for each XT-9100 in Position XT1.

Select DX-9100, DOWNLD, and XT. Enter the PC serial communication
port (1 or 2) in the “PC Port” field and press <Enter>.

Upload via the N2 Bus

Only one XT-9100 may be uploaded at one time and the configuration will
be stored under XT1. Select DX-9100, UPLOAD, and XT. Enter the
XT-9100 address (1-255) in the “Controller Address” field and the PC
serial communication point (1, 2) in the “PC Port” field. Press <Enter>.

XT-9100 configuration data can only be changed item by item with the
SX Tool. It is not possible to download or upload a complete
configuration.

Via the SX Tool