28 Configuration Guides—XT-9100 Configuration Guide

RI.

HI.

Type

R/W

Tag

Description

10

0A

1 Byte

R

DIS2

Digital Input Status XP2

X8 X7 X6 X5 X4 X3 X2 X1

X1 = 1

XP2 : Digital Input 1 is On

X2 = 1

XP2 : Digital Input 2 is On

X3 = 1

XP2 : Digital Input 3 is On

X4 = 1

XP2 : Digital Input 4 is On

X5 = 1

XP2 : Digital Input 5 is On

X6 = 1

XP2 : Digital Input 6 is On

X7 = 1

XP2 : Digital Input 7 is On

X8 = 1

XP2 : Digital Input 8 is On

11

0B

2 Byte

R

AIS

Analog Input Status

X16 X15 X14 X13 X12 X11 X10 X9 X8
X7 X6 X5 X4 X3 X2 X1

X1 = 1

AIH1

High Alarm Condition

X2 = 1

AIL1

Low Alarm Condition

X3 = 1

AIH2

High Alarm Condition

X4 = 1

AIL2

Low Alarm Condition

X5 = 1

AIH3

High Alarm Condition

X6 = 1

AIL3

Low Alarm Condition

X7 = 1

AIH4

High Alarm Condition

X8 = 1

AIL4

Low Alarm Condition

X9 = 1

AIH5

High Alarm Condition

X10= 1

AIL5

Low Alarm Condition

X11= 1

AIH6

High Alarm Condition

X12= 1

AIL6

Low Alarm Condition

X13= 1

AIH7

High Alarm Condition

X14= 1

AIL7

Low Alarm Condition

X15= 1

AIH8

High Alarm Condition

X16= 1

AIL8

Low Alarm Condition