Configuration Guides—XT-9100 Configuration Guide 7

Software Configuration

Software configuration involves the setting of all the Items of the
extension module to values which correspond to the intended application.
Typically, use the GX Tool to configure a system, and the SX Tool to
troubleshoot. To use these tools, refer to the GX-9100 Software
Configuration Tool for Windows User’s Guide (LIT-6364060)
and the
SX-9100 Service Module User’s Guide (LIT-6364070). Proceed in the
following order:

1.

Define XT-9100 type settings.

2.

Define XT-9100 configuration.

3.

Define analog input characteristics.

4.

Define digital input characteristics.

5.

Define analog output characteristics.

6.

Define digital output characteristics.

Via the GX Tool

Select DX-9100 and then Global. Enter the frequency as 50 or 60. The
XT frequency and the DX frequency are both defined here.

Via the SX Tool

Set Bit X1 of Item XTS (RI.69).

X1 = 0

50 Hz power line

X1 = 1

60 Hz power line

Via the GX Tool

First configure an XT Module. Select XTn, then Analog or Digital. Then
select the just configured XTn, XTn, and Data.

To set this flag, at the “Status on comm. fail” (communication failure)
field, enter 0 or 1.

When this bit is set to “0,” the digital outputs are switched off upon a
serial interface failure, and the corresponding Item values are reset to zero.

When set to “1,” the digital outputs hold their current state upon a serial
interface failure.

XT-9100 Type
Settings

Power Line
Frequency
(50 or 60 Hz)

Output
Hold/Reset on
Comm. Failure
Flag