16 Configuration Guides—XT-9100 Configuration Guide

The digital input transitions of XP1 are counted as follows:

Digital
Input
DIn

Prescale
PCn

Count
Transition

Pulse
Counter
CNTRn

(RI.09)

(RI.48-55)

(RI.32-39)

emcmxt-3

Figure 3: Counter Prescaler

A count transition occurs when the number of positive transitions of the
digital input (DIn) equals the value of the prescaler (PCn). The Pulse
Counter (CNTn) counts the count transitions (n = 1-8).

Note: Counters are only available in the XP1 location.

Via the GX Tool

Select XTn, DIn, then Data. At the “Prescaler (counts)” field, enter from 1
to 255. When the XT-9100 is connected to a DX-9100 Controller the total
counts can be read on the DX-9100 front panel.

Via the SX Tool

Enter the prescaler at Item PCn (RI. 48-55) within the range 1-255.

1.

When the XT-9100 is connected to a DX-9100 Controller, you can
view the DI status and counter values from the DX-9100 front panel.
See the Display Panel and Keypads section in the DX-9100 Extended
Digital Controller Technical Bulletin (LIT-6364020).

2.

The status of the digital inputs can be seen at Item DIS1 (RI.09), bits
X1-X8, and Item DIS2 (RI.10), bits X1-X8.

Each analog output is defined and configured by the following parameters:

Tag name (GX-9100 only)

Output type

When the XT is connected to a DX-9100 Controller, the following
parameters are defined in the DX-9100 for the analog output:

Source

Range

DI: Counter
Prescaler

DI Notes

Analog Output
Configuration