TABLE 3: POINTS LIST IN OBJECT ORDER

Read/

Write

BACnet

Object

Type

BACnet

Object

Inst

Descriptor

Default

Min

Max

Point Description

R/W

(2) AV

1

OCC_COOL_SP

72

45

99

Occupied Cooling Setpoint

R/W

(2) AV

2

UNOC_COOL_SP

85

45

99

Un-Occupied Cooling Setpoint

R/W

(2) AV

3

SAT_COOL_SP

50

40

65

Supply Air Temperature Limit for Cooling
Setpoint (degrees F)

R

(2) AV

4

SUP_AIR_TEMP

Supply Air Temperature

R

(2) AV

5

RET_AIR_TEMP

Return Air Temperature

R

(2) AV

6

SPACE_TEMP

Space (Indoor) Air Temperature

R

(2) AV

7

AMB_TEMP

Outside Air Temperature

R

(2) AV

8

IAQ_VALUE

Demand Ventilation (IAQ) Value (PPM)

R

(2) AV

9

OAQ_VALUE

1000

0

5000

Outside Demand Ventilation (OAQ) Value
(PPM)

R

(2) AV

10

AMB_AIR_HUM

Outside Air Humidity

R

(2) AV

11

AMB_AIR_ENTH

Outside Air Enthalpy

R

(2) AV

12

RET_AIR_HUM

Return Air Humidity

R

(2) AV

13

RET_AIR_ENTH

Return Air Enthalpy

R

(2) AV

14

ACC_OVER_TME

Accumulated Unoccupied Override Time (in
hours)

R

(2) AV

15

ACTIVE_ALARM

Active Alarm

R

(2) AV

16

NUMBER_COMPS

Number of Compressors Available

R

(2) AV

17

OP_COOL_STPT

Operating Cooling Setpoint

R/W

(2) AV

18

DEMVENT_STPT

1000

0

5000

Demand Ventilation Setpoint

R/W

(2) AV

19

ECON_MIN_POS

20

0

100

Economizer Minimum Position

R/W

(2) AV

20

ECO_1ST_STPT

55

40

65

Economizer First Stage Setpoint

R/W

(2) AV

21

ECO_2ND_STPT

50

40

65

Economizer Second Stage Setpoint

R/W

(2) AV

22

ECON_OAEN_SP

27

10

50

Economizer Outside Air Enthalpy Setpoint

R/W

(2) AV

23

ECON_OAT_ENA

55

40

80

Economizer Outside Air Temperature Enable
Setpoint

R/W

(2) AV

24

COM_V_HI_SP

80

60

85

Comfort Ventilation Upper Setpoint (degrees F)

R/W

(2) AV

25

COM_V_LOW_SP

70

60

85

Comfort Ventilation LowerSetpoint (degrees F)

R/W

(2) AV

26

TEM_HUM_STPT

50

20

80

Temperature/Humidity Setpoint (percent
Humidity)

R/W

(2) AV

27

HGR_HUM_STPT

50

0

100

Hot Gas Reheat Humidity Setpoint (percent
Humidity)

R/W

(2) AV

28

MAX_TH_OFSET

3

0

5

Max Temperature/Humidity Setpoint Offset

R/W

(2) AV

29

TH_OFFSET

5

1

10

Temperature/Humidity % Humidity that = 1°F
of Offset

R/W

(2) AV

30

MAX_DMV_ECON

50

0

100

Maximum Demand Ventillation Economizer
Position

R

(2) AV

31

ECO_DAMP_OUT

Economizer Damper Output Status (0-100%)

R

(2) AV

32

EXH_DAMP_OUT

Exhaust Damper Output Status (0-100%)

R

(2) AV

33

BLDG_STATIC

Building Static Pressure

R

(2) AV

34

SFAN_VFD_OUT

Supply Fan VFD Output Status (0-100%)

R

(2) AV

35

DUCT_STATIC

Duct Static Pressure

R

(2) AV

36

ALARM_1

System Alarm #1

R

(2) AV

37

ALARM_2

System Alarm #2

Advertising