Connection, Modbus connection – Simplicity LINC GATEWAY 514067-UAD-A-0509 User Manual

Page 2

Advertising
background image

514067-UAD-A-0509

2

Johnson Controls Unitary Products

CONNECTION

The Simplicity

®

LINC has 2 ports, one for connection to the BAS

network (BACnet) and one to the Simplicity

®

board (Modbus).

BACNET NETWORK

The only connection required in the field is to the BACnet (BAS)
network.

NOTE: Proper termination and grounding of the shields must

be observed.

DIP switches A0-A7 on the Simplicity

®

LINC board allow

selection of the MAC Address. The MAC Address identifies the
Simplicity

®

LINC to other devices and must be between 1 and

99. The default DIP switch setting is 1.

A Device Instance (DE) Modifier is used by the Simplicity

®

LINC

and defaulted to 230. The combination of the DE Modifier and
the default DIP switch setting creates a default DE of 23001.
The default Unit Name is YORK_RTU.

FIGURE 2: MAC ADDRESS EXAMPLES

DIP switches B0-B3 on the Simplicity

®

LINC board allow for

selection of the BACnet transfer speed.The default speed is set
at 38.4k baud. Other speeds can be chosen as shown in Table
1.

MODBUS CONNECTION

The UP device communicates with the Simplicity

®

LINC using

the Modbus RTU protocol on an RS485 connection. Connection
and addressing of the UP product is completed at the factory.
No further adjustment should be done.

If a problem arises with the Simplicity

®

LINC or a parameter not

exposed by the Simplicity

®

LINC requires modification, the UP

controller software can be manipulated using a Microsoft

©

Windows-based PC with the Simplicity

®

PC software

(downloadable from the UP website). To connect the PC to the
UP controller, a FREEnet USB adaptor (Part No.
S103101967000), which is an RS232 to RS485 adapter, and
FREEnet adapter cable (S102538682000) are required and
available through SOURCE1 (Toll-free at 1-800-536-6112).

SOFTWARE SETUP

The control sequence is managed by the Simplicity

®

controller.

The data points on these systems are mapped to standard AV
and BV BACnet Objects. As a preconfigured application, no
configuration is necessary in the Simplicity

®

LINC Gateway.

MAC Address of 21

1
0
4
0
16
0
0
0
21

1
2
0
0
0
32
64
0
99

MAC Address of 99

1
2
4
8

16
32
64

128

ON

1 2 3 4 5 6

7 8

1
2
4
8

16
32
64

128

ON

1 2 3 4 5 6 7 8

A0
A1
A2
A3
A4
A5
A6
A7

A0
A1
A2
A3
A4
A5
A6
A7

TABLE 1: BAUD RATE SELECTION SETTINGS

DIP Setting

Baud Rate

1

110

2

300

3

600

4

1200

5

2400

6

4800

7

9600

8

19200

9

20833

10

28800

11

38400

12

57600

13

76800

14

115200

The default Simplicity

®

board address is 1. Do not

engage the Address button on the Simplicity

®

board.

This changes the address and causes a Modbus
communication failure.