Simplicity LINC GATEWAY 514067-UAD-A-0509 User Manual

Page 4

Advertising
background image

514067-UAD-A-0509

4

Johnson Controls Unitary Products

TABLE 2: POINTS LIST IN DESCRIPTION ORDER

Read/

Write

BACnet

Object

Type

BACnet

Object

Inst

Descriptor

Default

Min

Max

Point Description

R

(2) AV

14

ACC_OVER_TME

Accumulated Unoccupied Override Time
(in hours)

R

(2) AV

15

ACTIVE_ALARM

Active Alarm

R

(5) BV

16

AIR_PROOF_SW

Air Proving Switch Status (1=closed,
0=open/no air flow)

R/W

(2) AV

79

OAQ_STPT

1000

0

5000

Air Quality Setpoint Outside

R

(5) BV

85

ALARM_1_ON

Alarm Buffer #1 (0=Alarm has cleared,
1=Alarm is still active)

R

(5) BV

86

ALARM_2_ON

Alarm Buffer #2 (0=Alarm has cleared,
1=Alarm is still active)

R

(5) BV

87

ALARM_3_ON

Alarm Buffer #3 (0=Alarm has cleared,
1=Alarm is still active)

R

(5) BV

88

ALARM_4_ON

Alarm Buffer #4 (0=Alarm has cleared,
1=Alarm is still active)

R

(5) BV

89

ALARM_5_ON

Alarm Buffer #5 (0=Alarm has cleared,
1=Alarm is still active)

R

(2) AV

33

BLDG_STATIC

Building Static Pressure

R

(5) BV

29

BP_SENS_INST

Building Static Pressure Sensor Installed

R/W

(2) AV

57

BLDG_SP_STPT

0.1

-0.25

0.25

Building Static Pressure Setpoint

R/W

(2) AV

25

COM_V_LOW_SP

70

60

85

Comfort Ventilation LowerSetpoint
(degrees F)

R

(5) BV

34

CVM_COOLING

Comfort Ventilation Mode for Cooling
Enabled

R

(5) BV

35

CVM_HEATING

Comfort Ventilation Mode for Heating
Enabled

R

(5) BV

33

COM_VENT_STA

Comfort Ventilation Mode Status (1=control
is in Comfort Vent mode, 0= it is not)

R/W

(2) AV

24

COM_V_HI_SP

80

60

85

Comfort Ventilation Upper Setpoint
(degrees F)

R

(5) BV

23

COOLING_ENA

Cooling Mode Enabled

R

(5) BV

21

FAN_ON_W_SEN

CV - Indoor Fan Operates with Space
Sensor Present Option Enabled

R

(2) AV

56

CV_VAV_SELEC

CV/VAV Selected (0= Valid CV, 1=Valid
VAV, 2= Invalid Value)

R

(2) AV

8

IAQ_VALUE

Demand Ventilation (IAQ) Value (PPM)

R

(5) BV

39

DEMAND_VENT

Demand Ventilation (using Inside Sensor)
Enabled

R/W

(2) AV

18

DEMVENT_STPT

1000

0

5000

Demand Ventilation Setpoint

R

(2) AV

67

REVISION

xx

Device Revision

R

(5) BV

90

DF_SW_INST

Dirty Filter Switch Installed

R

(5) BV

15

DIRT_FILT_SW

Dirty Filter Switch Status (0=open,1=closed/
fault)

R

(2) AV

35

DUCT_STATIC

Duct Static Pressure

R/W

(2) AV

58

DUCT_SP_STPT

1.5

0

5

Duct Static Pressure Setpoint

R/W

(2) AV

59

DUCT_SD_STPT

4.5

0

5

Duct Static Pressure Shutdown Setpoint

R

(2) AV

31

ECO_DAMP_OUT

Economizer Damper Output Status
(0-100%)

Advertising