TABLE 2: POINTS LIST IN DESCRIPTION ORDER (CONTINUED)

Read/

Write

BACnet

Object

Type

BACnet

Object

Inst

Descriptor

Default

Min

Max

Point Description

R/W

(2) AV

71

SPCE_ALM_TMP

0

0

25

Space Sensor Alarm Temperature (degrees
F, 0 = disabled)

R/W

(2) AV

72

SPCE_ALM_TIM

0

0

120

Space Sensor Alarm Time (minutes F, 0 =
disabled)

R

(5) BV

26

SEN_FAULT_EN

Space Sensor Fault Override (Construction
Mode) Enabled

R/W

(2) AV

73

SP_OFF_RANGE

3

0

5

Space Temprature Sensor Offset Range
(0-5 degrees)

R

(2) AV

4

SUP_AIR_TEMP

Supply Air Temperature

R/W

(2) AV

70

SAT_ALM_COOL

0

0

80

Supply Air Temperature Alarm Setpoint for
Cooling

R/W

(2) AV

53

SAT_ALM_HEAT

0

0

120

Supply Air Temperature Alarm Setpoint for
Heating

R

(5) BV

22

SAT_COOLING

Supply Air Temperature Limit for Cooling
Enabled

R/W

(2) AV

3

SAT_COOL_SP

50

40

65

Supply Air Temperature Limit for Cooling
Setpoint (degrees F)

R

(5) BV

24

SAT_HEATING

Supply Air Temperature Limit for Heating
Enabled

R/W

(2) AV

52

SAT_HEAT_SP

135

100

180

Supply Air Temperature Limit for Heating
Setpoint (degrees F)

R

(2) AV

34

SFAN_VFD_OUT

Supply Fan VFD Output Status (0-100%)

R

(2) AV

36

ALARM_1

System Alarm #1

R

(2) AV

37

ALARM_2

System Alarm #2

R

(2) AV

38

ALARM_3

System Alarm #3

R

(2) AV

39

ALARM_4

System Alarm #4

R

(2) AV

40

ALARM_5

System Alarm #5

R/W

(2) AV

29

TH_OFFSET

5

1

10

Temperature/Humidity % Humidity that =
1°F of Offset

R/W

(2) AV

26

TEM_HUM_STPT

50

20

80

Temperature/Humidity Setpoint (percent
Humidity)

R

(5) BV

67

FAN_HEAT

Turn OFF Continuous Fan when Starting
Heat Enabled (0=Continuous Fan ON)

R/W

(2) AV

2

UNOC_COOL_SP

85

45

99

Un-Occupied Cooling Setpoint

R/W

(2) AV

51

UNOC_HEAT_SP

60

45

99

Un-Occupied Heating Setpoint

R/W

(2) AV

75

UNOC_OVR_TP

60

0

240

Unoccupied Override Time Period

R/W

(2) AV

65

VAV_CL_LO_SP

55

40

70

VAV Cooling Supply Air Temperature: Lower
Setpoint (degrees F)

R/W

(2) AV

66

VAV_SAT_RSET

72

40

85

VAV Cooling Supply Air Temperature: Reset
Setpoint (Space Temperature)(degrees F)

R/W

(2) AV

64

VAV_CL_HI_SP

60

40

70

VAV Cooling Supply Air Temperature: Upper
Setpoint (degrees F)

R

(5) BV

5

VAV_OCC_HEAT

VAV Occupied Heating Enabled

R/W

(2) AV

60

VAV_OHEAT_SP

68

40

85

VAV Occupied Heating Setpoint (degrees F)