Simplicity LINC GATEWAY 514067-UAD-A-0509 User Manual

Page 7

Advertising
background image

514067-UAD-A-0509

Johnson Controls Unitary Products

7

TABLE 2: POINTS LIST IN DESCRIPTION ORDER (CONTINUED)

Read/

Write

BACnet

Object

Type

BACnet

Object

Inst

Descriptor

Default

Min

Max

Point Description

R

(5) BV

66

E_FREEZE_ST

Hot H2O Freeze Thermostat Switch #1
Input Status (1=closed, 0=open/fault)

R

(2) AV

55

HW_VLV_OUT

Hot Water Valve Output Status (0-100%)

R

(5) BV

2

HYDRONC_HEAT

Hydronic Heat Enabled

R

(5) BV

3

HH_REVER_VLV

Hydronic Heat Reverse Actuated Valve
Installed

R/W

(2) AV

62

HYD_S1_SA_SP

120

80

180

Hydronic Heating Stage #1 Supply Air
Setpoint (degrees F)

R/W

(2) AV

63

HYD_S2_SA_SP

150

80

180

Hydronic Heating Stage #2 Supply Air
Setpoint (degrees F)

R/W

(2) AV

80

IO_DVNT_STPT

700

0

2000

Indoor/Outdoor Demand Ventilation
Setpoint

R

(2) AV

45

I_C1_ACM_HRS

Intelli-Comfort Compressor #1 Accumulated
Run Time (in hours)

R

(5) BV

73

I_COMP1_STAT

Intelli-Comfort Compressor #1 Input Status
(0=output is OFF, 1=output is ON)

R

(2) AV

46

I_C2_ACM_HRS

Intelli-Comfort Compressor #2 Accumulated
Run Time (in hours)

R

(5) BV

76

I_COMP2_STAT

Intelli-Comfort Compressor #2 Input Status
(0=output is OFF, 1=output is ON)

R

(5) BV

79

I_CFAN_STAT

Intelli-Comfort Condenser Fan #1 Input
Status (0=output is OFF, 1=output is ON)

R

(5) BV

72

I_FAN_OVER

Intelli-Comfort Fan Overload Switch Input
Status (0=open,1=closed)

R

(5) BV

82

I_FREEZE_1

Intelli-Comfort Freeze Thermostat Switch #1
Input Status (0=open,1=closed)

R

(5) BV

83

I_FREEZE_2

Intelli-Comfort Freeze Thermostat Switch #2
Input Status (0=open,1=closed)

R

(5) BV

80

I_GAS_VLVE1

Intelli-Comfort Gas Valve #1 Input Status

R

(5) BV

75

I_HPS1

Intelli-Comfort High Pressure Switch for
Compressor #1 Input Status (1=closed,
0=open/fault)

R

(5) BV

78

I_HPS2

Intelli-Comfort High Pressure Switch for
Compressor #2 Input Status (1=closed,
0=open/fault)

R

(5) BV

71

I_IFAN_STAT

Intelli-Comfort Indoor Fan Output Status
(0=output is OFF, 1=output is ON)

R

(5) BV

81

I_LIMIT_1

Intelli-Comfort Limit Switch #1 Input Status

R

(5) BV

74

I_LPS1

Intelli-Comfort Low Pressure Switch for
Compressor #1 Input Status (1=closed,
0=open/fault)

R

(5) BV

77

I_LPS2

Intelli-Comfort Low Pressure Switch for
Compressor #2 Input Status (1=closed,
0=open/fault)

R

(5) BV

28

INTELLI-STRT

Intelli-Start Enabled

R/W

(5) BV

13

LOADSHED

Loadshed (0=clear loadshed, 1=set load-
shed operation)

R

(5) BV

19

LOW_AMB_OVRD

Low Ambient Temperature (0=comps not
overridden by LAT, 1=comps overridden)