Simplicity LINC GATEWAY 514067-UAD-A-0509 User Manual

Page 15

Advertising
background image

514067-UAD-A-0509

Johnson Controls Unitary Products

15

TABLE 3: POINTS LIST IN OBJECT ORDER (CONTINUED)

Read/

Write

BACnet

Object

Type

BACnet

Object

Inst

Descriptor

Default

Min

Max

Point Description

R

(5) BV

71

I_IFAN_STAT

Intelli-Comfort Indoor Fan Output Status
(0=output is OFF, 1=output is ON)

R

(5) BV

72

I_FAN_OVER

Intelli-Comfort Fan Overload Switch Input
Status (0=open,1=closed)

R

(5) BV

73

I_COMP1_STAT

Intelli-Comfort Compressor #1 Input Status
(0=output is OFF, 1=output is ON)

R

(5) BV

74

I_LPS1

Intelli-Comfort Low Pressure Switch for
Compressor #1 Input Status (1=closed,
0=open/fault)

R

(5) BV

75

I_HPS1

Intelli-Comfort High Pressure Switch for
Compressor #1 Input Status (1=closed,
0=open/fault)

R

(5) BV

76

I_COMP2_STAT

Intelli-Comfort Compressor #2 Input Status
(0=output is OFF, 1=output is ON)

R

(5) BV

77

I_LPS2

Intelli-Comfort Low Pressure Switch for
Compressor #2 Input Status (1=closed,
0=open/fault)

R

(5) BV

78

I_HPS2

Intelli-Comfort High Pressure Switch for
Compressor #2 Input Status (1=closed,
0=open/fault)

R

(5) BV

79

I_CFAN_STAT

Intelli-Comfort Condenser Fan #1 Input
Status (0=output is OFF, 1=output is ON)

R

(5) BV

80

I_GAS_VLVE1

Intelli-Comfort Gas Valve #1 Input Status

R

(5) BV

81

I_LIMIT_1

Intelli-Comfort Limit Switch #1 Input Status

R

(5) BV

82

I_FREEZE_1

Intelli-Comfort Freeze Thermostat Switch #1
Input Status (0=open,1=closed)

R

(5) BV

83

I_FREEZE_2

Intelli-Comfort Freeze Thermostat Switch #2
Input Status (0=open,1=closed)

R

(5) BV

85

ALARM_1_ON

Alarm Buffer #1 (0=Alarm has cleared,
1=Alarm is still active)

R

(5) BV

86

ALARM_2_ON

Alarm Buffer #2 (0=Alarm has cleared,
1=Alarm is still active)

R

(5) BV

87

ALARM_3_ON

Alarm Buffer #3 (0=Alarm has cleared,
1=Alarm is still active)

R

(5) BV

88

ALARM_4_ON

Alarm Buffer #4 (0=Alarm has cleared,
1=Alarm is still active)

R

(5) BV

89

ALARM_5_ON

Alarm Buffer #5 (0=Alarm has cleared,
1=Alarm is still active)

R

(5) BV

90

DF_SW_INST

Dirty Filter Switch Installed

R

(5) BV

93

OCC_COMS_ENA

Occupied Thermostat or Communication
Input Enabled

R/W

(5) BV

96

MANUAL_WRITE

Manual Write Command to ModlINC