4 setpoints and sequence, Setpoints, T[°c – Siemens RDG400 User Manual

Page 11

Advertising
background image

11 / 42

Siemens

RDG100, RDG100T, RDG110, RDG140, RDG160 Basic Documentation

CE1P3182en

Building Technologies

Functions

28 May 2009

4.4

Setpoints and sequence

In single-duct changeover applications the Comfort setpoints for heating and
cooling sequence are the same (w).

In applications with electrical heater, radiator or heating / cooling coil the Comfort
setpoint is at the heating sequence.
The start of the cooling sequence is linked to “Dead-zone” above the Comfort
setpoint. The dead zone can be set via parameter P33.

The setpoints for Energy Saving and Protection mode are below the Comfort
setpoints (heating) and above the Comfort setpoints (cooling).
They can be set via parameters P11, P12 (Energy Saving) and P65, P66
(Protection).

The control signal for air flow can be limited via parameters P63 and P64.
See section 4.8.1.
To simplify the diagram below, only minimum limitation is shown.

w

31

81D

127

T[°C]

w

HeatProt

w

CoolProt

w

HeatEco

w

CoolEco

Comfort mode

Energy Saving / Protection mode

Application

Heating mode

Cooling mode

Heating mode

Cooling mode

Single duct

Single duct
with min/max
limitation


Comfort mode

Energy Saving

Protection mode

Application

Single duct
with
electrical
heater

Single duct
with radiator



Y

T

W

YR

Y

T

W

HeatProt

W

CoolProt

YR

Y

T

W

HeatEco

W

CoolEco

YR

Y

T

W

HeatProt

W

CoolProt

YE

Y

T

W

HeatEco

W

CoolEco

YE

Y

T

W

YE

Y

T

W

CoolProt

W

CoolEco

Y

T

W

HeatProt

W

HeatEco

Y

T

W

HeatProt

W

HeatEco

Y

T

W

Y

T

W

Y

T

W

CoolProt

W

CoolEco

Y

T

W

Y

T

W

Advertising