9 multifunctional input, digital input, 9 “multif, 9 “multi – Siemens RDG400 User Manual

Page 26: 9 “multifuncti, Ction 4.9 “multifuncti

Advertising
background image

26 / 42

Siemens

RDG100…/RDG110…/RDG140.../RDG160… Basic Documentation

CE1P3182en

Building Technologies

Functions

28 May 2009

4.9

Multifunctional input, Digital input

The thermostat offers two multifunctional inputs X1 and X2 and a digital input D1.
A sensor of type NTC like QAH11.1 (AI, analog input) or a switch (DI, digital input)
can be connected to the input terminals. The functionality of the inputs can be
configured via parameters P38 for X1, P40 for X2, and P42 for D1.

# Function of input

Description

Type

X1/X2

Type

DI

0 Not used

No function.

--

--

1 External/Return

air temp.

Sensor input for external room temperature sensor or
return air temperature sensor to measure the current
room temperature, or floor heating temperature
sensor to limit the heating output.
Note: The room temperature is measured by the built-
in sensor if the floor heating limitation function is
enabled via parameter P51.

AI

2 Heat/cool

changeover

Sensor input for automatic heating / cooling
changeover function.
A switch can also be connected rather than a sensor
(switch closed = cooling, see section 4.6).

AI/(DI)

DI

3 Operating

mode

switchover

Digital input to switch over the operating mode to
Energy Saving.
If the operating mode switchover contact is active,
user operations are ineffective and “OFF” is displayed.

DI DI

4 Dewpoint monitor

Digital input for a dewpoint sensor to detect
condensation. Cooling is stopped if condensation
occurs.

DI DI

5 Enable

electrical

heater

Digital input to enable/disable the electrical heater via
remote control.

DI DI

6 Fault

Digital input to signal a fault.
If the input is active, “ALx” is displayed
(Alarm x, with x = 1 for X1, x = 2 for X2, x = 3 for D1).
Note: Fault displays do not influence the thermostat's
operation. They merely represent a visual signal.
Example: dirty air filter

DI DI


Operational action can be changed between normally open (N.O.) and normally
closed (N.C.) via parameter P39, P41 (or P43 if it is a digital input).
Each input X1, X2 or D1 must be configured with a different function (1 … 5).
Exception: one or two or three inputs may be configured as alarm inputs (6)

X1 is factory-set to “External sensor” (1), X2 to “Heating/Cooling changeover” (2),
and D1 to Operating mode changeover (3).

For more information see section 4.5 “Applications”.


Advertising