7 control sequences, 1 applications and sequences, 2 sequences overview (setting via parameter p01) – Siemens RDG400 User Manual

Page 17

Advertising
background image

17 / 42

Siemens

RDG100, RDG100T, RDG110, RDG140, RDG160 Basic Documentation

CE1P3182en

Building Technologies

Functions

28 May 2009

4.7

Control sequences

4.7.1

Applications and sequences


Application VAV

Sequences

Single duct

h ( \ ), c ( / )

Single duct & electrical heater

el.h + c (



\ / )

Single duct & radiator

rad + c ( r\ / ),

Single duct with heat/cool coil

h + c ( \ / )


4.7.2

Sequences overview (setting via parameter P01)

The sequence can be set via parameter P01, if available.
The thermostats can be used in systems featuring:
• Heating only mode (P01=0)
• Cooling only mode (P01=1)
• Manual heating/cooling changeover (P01=2)
• Automatic heating/cooling changeover (P01=3)
• Heating and cooling mode (e.g. 4-pipe system) (P01=4)

The available modes depend on the application
(selected via DIP switch, see section 4.5).

Parameter

P01 = 0

P01 = 1

P01 = 2

P01 = 3


Sequence

T °C

T °C

T °C

T °C

T

Mode

Available for:

Heating mode

Cooling mode

Manually select
heating or
cooling mode

Automatic
heating/cooling
changeover via
external water
temperature
sensor or
remote switch

Single duct

1)

1)

Single duct &
electrical heater

3) 3) 3) 3)

Single duct &
radiator

3) 3) 3) 3)

Single duct with
heat/cool coil

2)

2)


1) Changeover air
2) Changeover water; heat/cool coil
3) The controller operates in heating AND cooling mode. P01 is not available

Notes

Advertising