1 parameters service level, Handling of faults, Dip switches – Siemens RDG400 User Manual

Page 29

Advertising
background image

29 / 42

Siemens

RDG100, RDG100T, RDG110, RDG140, RDG160 Basic Documentation

CE1P3182en

Building Technologies

Functions

28 May 2009

4.12.1 Parameters Service level

Pa

ra

m

et

er

Name

Factory setting

Range

RDG

400

Service level

P01

Control sequence

When 2-pipe /
2-stage:
1 = Cooling only
When 4-pipe:
4 = H and C

0 = Heating only
1 = Cooling only
2 = H/C changeover manual
3 = H/C changeover auto
4 = Heating and Cooling

P02

User operating mode profile (mode button)

1

1 = (Auto) - Comfort - Protection
2 = (Auto) - Comfort - E Saving - Prot

P04

Selection of °C or °F

0 (°C)

0 = Degrees Celsius (°C)
1 = Degrees Fahrenheit (°F)

P05

Sensor calibration (intern, extern)

0 K

– 3 ... 3 K

P06

Standard temperature display

0

0 = Room Temperature
1 = Setpoint

P07

Display info line
(2nd line of LCD)

0

0 = --- (No display)
1 = °C and °F

0..1

P08

Comfort setpoint

21 °C

5 ... 40 °C

P09

Minimum setpoint in Comfort mode

5 °C

5 ... 40 °C

P10

Maximum setpoint in Comfort mode

35 °C

5 ... 40 °C

P11

Energy Saving heating setpoint

15 °C

OFF, 5 ... WcoolE-saving;
(WcoolE-saving = 40 °C max)

P12

Energy Saving cooling setpoint

30 °C

OFF, WHeatE-saving ... 40 °C;
(WHeatE-saving = 5 °C min)

P14

Button lock function

0

0 = Unlocked
1 = Auto locked
2 = Manual locked


Parameter display depends on selected application and function



Note

Advertising