Single duct with heating / cooling coil – Siemens RDG400 User Manual

Page 24

Advertising
background image

24 / 42

Siemens

RDG100…/RDG110…/RDG140.../RDG160… Basic Documentation

CE1P3182en

Building Technologies

Functions

28 May 2009

4.8.2 Control output for electrical heater, radiator and heating /

cooling coil


The valve receives an OPEN/ON command via control output Y1
1. When the acquired room temperature is below “setpoint” (heating mode) or

above the setpoint (cooling mode)

2. When the control outputs have been inactive for more than the “Minimum output

off-time” (factory setting 1 minute, adjustable via parameter P48).


OFF command for valve output:
1. When the acquired room temperature is above the setpoint (heating mode) or

below the setpoint (cooling mode).

2. When the valve has been active for more than the “Minimum output on-time”

(factory setting 1 minute, adjustable via parameter P49).


The electrical heater receives an ON command via the auxiliary heating control
output (Y1):
1. When the acquired room temperature is below “setpoint for electric heater”.
2. When the electrical heater has been switched off for at least 1 minute.

The OFF command for the electrical heater is output:
1. When the acquired room temperature is above the setpoint (electric heater).
2. When the electrical heater has been switched on for at least 1 minute.


A safety thermostat (to prevent overheating) must be provided externally.


• The demand calculated by PI control from the current room temperature and

setpoint is provided via Y10 as a continuous DC 0 ... 10 V signal.

• The signal converter (SEM61.4) converts the DC 0 ... 10 V signal to AC 24 V

PDM pulses for the current valve

• The current valve (SEA45.1) supplies the el. heater with AC 50 … 660 V pulsed

current.

Y

E

DC 0 ... 10 V

Y1 G

L

N

Y1

L

Q

5.7 kW
max.

N1

U1

FF

F...

Y1

K...

G0

G

G

31

81

D

2

1

G

G0

Y

PWM

AC 24 V

N1 RDG400
U1

Signal converter SEM61.4

(see data sheet N5102)

Y1

Current valve SEA45.1

(see data sheet N4937)

K… Safety "chain", e.g. safety thermostat and high-temperature cut-out
FF

Very fast-acting fuse

F… Overcurrent

trip

ON/OFF control signal
(2-position)

Electrical heater
control signal

(2-position)

Caution

DC 0 ... 10 V
for el. heaters

Advertising