Parameters service level – Siemens RDG400 User Manual

Page 31

Advertising
background image

31 / 42

Siemens

RDG100, RDG100T, RDG110, RDG140, RDG160 Basic Documentation

CE1P3182en

Building Technologies

Functions

28 May 2009

Param

et

er

Name

Factory setting

Range

RDG400

Diagnostics & test

d01

Application type

Diagnostics

0:= --- (No application)
1:= Single-duct
2:= Single-duct with el. heater
3:= Single-duct with radiator
4:= Single-duct with h/c coil

d02

X1 status

Diagnostics

0 = Not activated (for DI)
1 = activated (DI)
0…49 °C = cur. temp. value (for AI)
00 = HC input short
100 = HC input open

d03

X2 status

Diagnostics

0 = Not activated (for DI)
1 = activated (DI)
0…49 °C = cur. temp. value (for AI)
00 = HC input short
100 = HC input open

d04

D1 status

Diagnostics

0 = Not activated (for DI)
1 = activated (DI)
00 = HC input short
100 = HC input open

d05

Test mode for checking the Y1/Y2
actuator direction
(press left button to escape)

---

“---“ = no signal on outputs Y1 and Y2
OPE = output Y1 forced open
CLO = output Y2 forced closing