MR0012J

9710 System Assurance Guide

A-5

Power usage for library without

drives

1

Watts 150 peak / 100 Continuous
KVA 0.15 Peak / 0.10 Continuous

Power usage for each 4890 drive

1

Watts 270 Peak / 230 Continuous
KVA 0.27 Peak / 0.23 Continuous

Power usage for each DLT drive

1

Watts 70 Peak / 60 Continuous
KVA .070 Peak / .060 Continuous

Heat output for library without
drives

680 BTU/hr

Heat output for each 4890 drive

880 BTU/hr

Heat output for each DLT drive

257 BTU/hr

Note:

1

Up to six drives take power from the 9710. Four additional drives take power from

the PDU box. Power ratings for the 9710, and (separately) for the PDU, are figured
by also adding the number of drives connected to each. The PDU box by itself has
zero load.

Table A-5. Power Characteristics (Continued)