3 setting the digital positioner 14, 3 setting the digital positioner – Samson Electri Actuator Type 3374 EB 8331-1 EN User Manual

Page 14

Advertising
background image

4.3 Setting the digital positioner

In the actuator version with digital

positioner, the travel is calibrated automati-

cally, allowing the travel (controlled variable

x) and the input signal (reference variable

w) of the positioner to be matched in the

best possible way. Additionally, the digital

positioner provides valve position feedback

for remote transmission.
Setting and start-up can be carried out using

four different operating modes. Operating

modes 1 and 2 work with set data stored in

the positioner's memory. The user only

needs to select the operating mode via the

selector switch (2) and press the button (4)

to start travel calibration.

Note: Setup with operating modes 3 and 0

=

can only be performed using a

SAMSON memory pen as the storage me-

dium, or in connection with SAMSON's

TROVIS-VIEW Configuration and Operator

Interface software and a PC or bus system.

Setup with operating modes 3 and 0 =

is

described in Mounting and Operating In-

structions EB 8331-2 EN.

Settings for operating modes 1 and 2

Increasing characteristic: actuator stem re-

tracts or extends as the input signal in-

creases.
After the actuator has been mounted on the

valve as described in section 2.2 and the

electrical connections have been established

as described in section 3, proceed as fol-

lows:

1. Set selector switch (2) with the arrow

pointing to operating mode 0 =
(closed-loop operation switched off).

2. Check mounting position of the potenti-

ometer gear (12).

The gear must be put onto the potentiometer

shaft to correspond with the rated travel of

the valve. The inscription Nennhub 15 or B

(for 6 to 19 mm travel) or Nennhub 30 or A

(for 6 to 35 mm travel) must be legible from

above on the associated gear side. If this is

not the case, pull the gear off the shaft and

put it back on again with the reverse side

facing upwards, allowing the intermediate

gear to engage properly.

NOTICE

Actuators with fail-safe action "Actuator

stem retracts" or "extends" are only de-

signed for a rated travel of 15 mm. Do not

reposition the gear!

Make sure that the shaft of the potentiometer

(12.1) is adjusted correctly.
3. Switch on power supply and set the in-

put signal to a current > 4 mA.

4. Set selector switch (2) with the arrow

pointing to operating mode 1 for 4 to
20 mA or 2 to 10 V input and alarm
signal, or set it to operating mode 2 for
0 to 20 mA or 0 to 10 V input and
alarm signal.

5. Press button (4) to start travel calibra-

tion.

14

EB 8331-1 EN

Operation and setting

Advertising