2 installation 8, 1 mounting position 8, 2 attachment to the valve 8 – Samson Electri Actuator Type 3374 EB 8331-1 EN User Manual

Page 8: 2installation 2.1 mounting position, 2 attachment to the valve

Advertising
background image

2

Installation

2.1 Mounting position

Installation depends on the mounting posi-

tion of the valve. However, do not install the

actuator suspended downwards.

Note: Manual override is only possible in

actuators with fail-safe action when the

power supply is connected (see section 4.1).

2.2 Attachment to the valve

Series V2001 (DN 15 to 80),

Type 3260 Valve (DN 65 to 150) and

Type 3214 Valve (DN 65 to 100)

1. Remove protective covers and unscrew

nut (6) from the valve.

2. Retract actuator stem slightly using the

manual override.
Place actuator with yoke onto the valve
and fasten with the nut (6, SW 36) using
a minimum tightening torque of
150 Nm.

3. When the plug stem (5) fits closely onto

the actuator stem (3), attach both stem
connector clamps (4) and fasten with
screws.

Series 240

1. Push plug stem down to close the valve.
2. Turn stem connector nut (8) until a dis-

tance of x = 75 mm (x = 90 mm for
DN 100 and larger) between the top of
the yoke and the top of the stem connec-

tor nut (8) is reached. Secure position
with lock nut (9).

3. Place actuator onto valve bonnet (2.3)

and fasten with ring nut (7).
If necessary, retract actuator stem
slightly beforehand using the manual
override.

4. When the stem connector nut (8) fits

closely onto the actuator stem, attach
both stem connector clamps (4) and
screw tight.

5. Move actuator stem (3) to the end posi-

tion (valve closed) using the manual
override or motor.

6. Align travel indicator scale (10) to the

middle of the stem connector (4) and
screw tight.

Type 3214 (DN 125 to 250)

1. Place actuator onto the valve and secure

with the ring nut (7). If necessary, retract
actuator stem slightly beforehand using
the manual override.

2. When the plug stem fits closely onto the

actuator stem (3), attach both stem
connector clamps (4) and screw tight.

3. Move actuator stem (3) to the end posi-

tion (valve closed) using the manual
override or motor.

4. Align travel indicator scale (10) to the

middle of the stem connector (4) and
screw tight.

8