5 retrofitting additional electrical equipment 17, 5retrofitting additional electrical equipment – Samson Electri Actuator Type 3374 EB 8331-1 EN User Manual

Page 17

Advertising
background image

Setting with limited travel range

Travel calibration is usually based on the

maximum travel of the valve.
If, however, the maximum possible travel is

to be limited to a smaller travel end value,

press the button (4) once at the start of cali-

bration while the signal lamp blinks for

10 seconds. As a result, travel calibration

via the potentiometer gear with rated travel

15 or 30 is limited to 6 mm. Each time the

button is pressed, the travel range is in-

creased by 1 mm.
If, for example, a valve designed for 15 mm

is to be operated with a limited travel range

of 10 mm, press the button (4) five times

during the 10 second time limit. The top sig-

nal lamp (8) flashes each time the key is

pressed.

Reporting defined events

At the binary output (terminal 83 and 84),

predefined events can be indicated (see

EB 8331-2 EN) during positioner operation

and transmitted to a control room.

5

Retrofitting additional

electrical equipment

CAUTION!

When installing electrical equipment, make

sure the power supply and the signal input

are disconnected. Only use power interrup-

tion devices which are protected against un-

intentional reconnection of the power sup-

ply.

Note: We recommend to apply a small

amount of lubricant (e.g. Vaseline) to the

spindles on the gear faces and to the sides

of the cogs.

The actuator can be subsequently equipped

with two limit contacts, two resistance trans-

mitters or a digital positioner.
Depending on the actuator version used, the

actuator PCB needs to be replaced as well

(see sections 5.2, 5.3 and 5.4).
The actuator version is marked on the name-

plate, e.g. Var.-ID 1063729.
When ordering additional electrical equip-

ment from the manufacturer, include this

model number in the order.
To install the limit contacts, resistance trans-

mitters or a digital positioner, the basic unit

(1400-8829) is required.

EB 8331-1 EN

17

Retrofitting additional electrical equipment

Advertising