5.4 Digital positioner

To install a positioner, a corresponding ac-

tuator PCB and the TROVIS-VIEW software

as well as a connecting cable (1400-7699)

are necessary.

Note: Actuators with a digital positioner

cannot be equipped with resistance transmit-

ters.

1. Remove the fastening screws. Push the

actuator board (1) from its guiding to
the right. Take out the board and re-
place it with a board with positioner.

2. Clip the spindle gear (2) onto the sleeve

(3) as illustrated at the top of Fig. 12
(top). Make sure the lateral latch is prop-
erly engaged in the groove of the sleeve.

3. Plug intermediate gear (5) onto the spin-

dle (4). Place the serrated ring (10) on
top and push it down as far as it will go.

Note: At this point, follow the instructions

described in section 5.1.2 on page 18 when

a new intermediate plate (index 6) is used.

4. The gear (12) on the feedback potenti-

ometer, which is equipped with a retain-
ing ring, must be put onto its shaft corre-
sponding with the rated travel of the
valve. The rated travel inscription
'Nennhub 15' or B (on the upper side
with the retaining ring) or 'Nennhub 30'
or A (lower side) must be legible from
above (also see Figs. 5 and 6).

5. Push the actuator board (1) back into its

guiding. Make sure that the gears are
properly engaged. Fasten the board us-
ing screws.

5.4.1 Calibrating the positioner

EB 8331-1 EN

23

Retrofitting additional electrical equipment

Fig. 12 · Version with positioner

without (top) and with (bottom) limit contacts

5

Intermediate gear

6

Contact cam

7

Cam bracket

8

Adjustment gears

10 Serrated ring
12 Gear feedback potentiometer

8

7

5

10

12

Advertising