Press the button briefly to obtain a travel cal-

ibration for valve CLOSED when the actua-

tor stem extends.

Direction of action: Increasing/increasing.
Hold the button pressed for longer than

three seconds (indicated by switchover from

signal lamp 8 to signal lamp 9) to obtain a

travel calibration for valve CLOSED when

the actuator stem retracts.

Direction of action: Increasing/decreasing.

CAUTION!

The automatic travel calibration lasts

approximately twice as long as the

actuator's transit time. During this

period, the valve leaves its current

position. Calibrate the travel either

on the test bench or when the

shut-off valves in the plant are

closed.

EB 8331-1 EN

15

Operation and setting

Fig. 6 · Selector switch and position of potentiometer gears in version with digital positioner

12

12.1

B

Stellungsregler

Positioner

Régulateur de position

SAMSON

10

9

11

6

5

2

1

3

4

3

1

7

2

8

1

Operating mode 1

2

Selector switch

3

Operating mode2

4

Travel calibration button

5

Operating mode 0

6

Operating mode 3

7

Potentiometer counter-

clockwise or clockwise

8

Signal lamp

9

Signal lamp

10

Actuator stem extends
and retracts

11

Interface jack

12

Potentiometer gear

12.1 Potentiometer shaft

Intermediate gear

Gear (12)

Position for 15 mm

rated travel (B)

Gear (12)

Position for 30 mm

rated travel (A)

Intermediate gear

Rated travel

inscription

Intermediate gear