EB 8331-1 EN

7

Design and principle of operation

Digital positioner

1)

Operating mode 1

Operating mode 2

Operating mode 3

Input signal

2)

Range

4...20 mA, Ri = 0.05 k

W

2...10 V, Ri = 10 k

W

0...20 mA, Ri = 0.05 k

W

0...10 V, Ri = 10 k

W

As per settings

3)

Resolution

10 Bit

Position feedback

signal

4)

Range

4...20 mA, R

B

0.2

£

k

W

2...10 V, R

B

³

5 k

W

0...20 mA, R

B

£

0.2 k

W

0...10 V, R

B

³

5 k

W

As per settings

3)

Resolution

8 Bit

Characteristic

Increasing, actuator stem retracts or extends

as the input signal increases

As per settings

3)

Travel

Adjustable

6 to 19 mm at 15 mm rated travel

6 to 35 mm at 30 mm rated travel

Setting

Using travel calibration button

(1 mm each time the button is pressed)

As per settings

3)

using button

1 binary input

Electrically isolated, switching voltage 18 to 30 V DC, approx. 7 mA

1 binary output

Electrically isolated semiconductor contact, max. 45 V DC,

min. 3 V DC, max. 25 mA

Integrated interface for SAMSON

memory pen/PC

Data transmission including settings, operating status and alarms

Transfer protocol: SAMSON SSP protocol

Total delay time

Approx. 30 ms

Accuracy

£

2.5 %

without taking the dead band into account

1)

Maximum two current inputs may be switched in series

2)

Maximum values ±50 mA or ±25 V

3)

SAMSON TROVIS-VIEW Operator Interface software, SAMSON memory pen

Advertising