20

5. Refrigerant Tubing

5-1. Use of the Flaring Method

Many of the conventional split system air conditioners

employ the flaring method to connect refrigerant tubes

which run between indoor and outdoor units. In this

method, the copper tubes are flared at each end and

connected with flare nuts.

5-2. Flaring Procedure with a Flare Tool

(1) Cut the copper tube to the required length with a

tube cutter. It is recommended to cut approx. 12" to

20" (30 to 50 cm) longer than the tubing length you

estimate.

(2) Remove burrs at the end of the copper tube with a

tube reamer or file. This process is important and

should be done carefully to make a good flare.

(Fig. 47)

When reaming, hold the tube end downward and be

sure that no copper scraps fall into the tube. (Fig. 48)

(3) Remove the flare nut from the unit and be sure to

mount it on the copper tube.

(4) Make a flare at the end of copper tube with a flare

tool.* (Figs. 49a and 49b)

(*Use “RIGID” or equivalent.)

A good flare should have the following characteristics:

inside surface is glossy and smooth.

edge is smooth.

tapered sides are of uniform length.

5-3. Caution before Connecting Tubes Tightly

a)

Be sure to apply a sealing cap or water-proof tape

to prevent dust or water from getting into the tubes

before they are used.

b)

Be sure to apply refrigerant lubricant to the match-

ing surfaces of the flare and union before connect-

ing them together. This is effective for reducing gas

leaks. (Fig. 50)

c)

For proper connection, align the union tube and

flare tube straight with each other, then screw in the

flare nut lightly at first to obtain a smooth match.

(Fig. 51)

NOTE

NOTE

Deburring

Before

After

Fig. 47

Reamer

Copper
tubing

Fig. 48

Flare tool

Flare nut

Copper
tubing

Fig. 49b

Fig. 49a

Apply refrigerant
lubricant here and here

Fig. 50

Flare nut

Union

Fig. 51

0 to 0.0196"
(0 to 0.5 mm)

If the special R410A
flare tool is used:

0.0472" (1.2 mm)

If the previous flare tool
(clutch-type) is used:

Adjust so that the amount of tube
protrusion is as shown in the figure.