Troubleshooting, 2. method of self-diagnostics, Procedure – Sanyo CL2472 User Manual

Page 46

Advertising
background image

1HR.

TIMER

button

ON/OFF

operation

button

ACL

(Reset)

button

ION

button

< Clock display >

Test run mode

Self-diagnostics mode

9. TROUBLESHOOTING

9-1. Precautions before Performing Inspection or Repair

NOTE

After checking the self-diagnostics monitor, turn the power OFF before starting inspection or repair.
High-capacity electrolytic capacitors are used inside the outdoor unit controller (inverter). They retain an electrical charge

(charging voltage DC 310V) even after the power is turned OFF, and some time is required for the charge to dissipate. Be

careful not to touch any electrified parts before the controller LED (red) turns OFF.
If the outdoor controller is normal, approximately 30 seconds will be required for the charge to dissipate. However, allow

at least 5 minutes for the charge to dissipate if there is thought to be any trouble with the outdoor controller.

1: If the operation lamp blinks every 0.5 seconds immediately when the

power is turned ON, there is an external ROM (OTP data) failure on the

indoor circuit board, or a ROM socket insertion problem, or the ROM

has not been installed.

2: The failure mode is stored in memory even when the power is not ON.

Follow the procedure below to perform diagnostics.

9-2. Method of Self-Diagnostics

Follow the procedure below to perform detailed trouble diagnostics.

PROCEDURE

Step 1: Press and hold the remote controller ION button and 1 HR TIMER

button. Then, press and hold the ACL (reset) button with a pointed

object such as the tip of a pen. After 5 seconds, release ACL

button first, then release ION and 1 HR TIMER buttons, "oP-1"

(test run) appears, blinking in the remote controller clock display

area.

Step 2: Next, press the 1 HR TIMER button once to change the display

from "oP-1" to "oP-3" (self-diagnostics). (The display continues to

blink.)

Step 3: Finally press the ON/OFF button to engage self-diagnostics mode.

• The self-diagnostics function utilizes the 3 indicator lamps on the main

unit, in combinations of ON lamps, blinking lamps, and OFF lamps, to

report the existence of sensor trouble or a protective operation. (The

lamps blink or remain ON for 5 seconds, then turn OFF for 2 seconds.)

Self-diagnostics is completed when the buzzer sounds 3 short beeps.

• A maximum of 3 self-diagnostics reports are displayed, for 5 seconds

each, beginning with the most recent report. Following this display the

lamps turn OFF. In order to view the self-diagnostics results again,

press the ON/OFF button again.

• The 3 lamps remain OFF if no trouble has occurred.

<IMPORTANT> After self-diagnostics is completed, be sure to press the

ACL (reset) button to return to normal mode. The air

conditioner will not operate if this is not done.

After turning on power to the air conditioner, use the remote controller and

follow the steps below to execute self-diagnostics.

46