Sanyo CL2472 User Manual

Page 112

Advertising
background image

23

(5) With the vacuum pump still running, close the “Lo”

knob of the manifold valve. Then stop the vacuum

pump.

(6) With the accessory hex wrench, turn the valve stem

on the narrow tube service valve counter-clockwise

by 90 degrees (1/4 turn) for 10 seconds, and then

turn the stem clockwise to close it again. (Fig. 58)

(7) Leak test all joints at the tubing (both indoor and out-

doors) with soapy water. Bubbles indicate a leak. Tight-

en the joint more when leaks, then check if there is no

leak. Be sure to wipe off the soap with a clean cloth.

(8) With the hex wrench, turn the wide tube service

valve stem counter-clockwise to fully open the valve.

(9) Turn the narrow tube service valve stem counter-

clockwise to fully open the valve.

(10) Loosen the vacuum hose connected to the wide

tube service port slightly to release the pressure.

Then, remove the hose.

(11) Fasten the valve cap on the wide tube service port

securely with an adjustable wrench or box wrench.

Next, mount the valve cap on the service valve and

tighten it to 170 lbs·in (200 kgf·cm) with a torque

wrench. This process is very important to prevent

gas from leaking from the system.

(12) Test run the air conditioner. (See next page.)

(13) While the air conditioner is running, apply liquid

soap to check for any gas leaks around the service

valves or caps.

(14) If there is no leakage, stop the air conditioner.

(15) Wipe off the soap on the tubing.

This completes air purging with a vacuum pump and the

air conditioner is ready for actual operation.

CAUTION

Be sure to completely insert

the hex wrench before

attempting to turn the valve.

Fig. 58

CAUTION

This may cause the refriger-

ant gas to leak. In order to

avoid this, take off the hose

quickly.

90° (1/4 turn)

Narrow tube

Hex wrench

Wide tube

Valve cap

Vacuum hose to manifold valve

07-154 CL1872-2472 6/12/07 3:19 PM Page 23

Advertising
This manual is related to the following products: