3 bus connectors – Siemens SIMATIC NET PROFIBUS User Manual

Page 130

Advertising
background image

Passive Components for RS-485 Networks

4-32

PROFIBUS Networks SIMATIC NET

6GK1970-5CA20-0AA1 Release 2 05/2000

4.3

Bus Connectors

Uses

Using the bus connector for SIMATIC NET PROFIBUS:

S

Nodes with an electrical 9-pin sub-D interface complying with EN 50170 can be
connected directly to the SIMATIC NET PROFIBUS cables

S

Electrical segments or individual nodes can be connected to the optical link
module (OLM, OBT).

S

Nodes or programming devices can be connected to a repeater.

Note

The integrated bus terminators and the mechanical specifications of the SIMATIC
NET bus connectors are tailored to the SIMATIC NET PROFIBUS cables (cable
type A of the PROFIBUS standard EN 50170-1-2). Fitting bus connectors to
cables with different electrical or mechanical properties can cause problems during
operation!

Advertising