10 help with problems during operation, 1 status displays for incorrect operation – Siemens SIMATIC NET PROFIBUS User Manual

Page 383

Advertising
background image

Infrared Link Modul (ILM)

6ZB5530–3AC30–0BA1

41

Copyright

by Siemens

10

Help With Problems During Operation

10.1

Status Displays for Incorrect Operation

LED Display

Possible Causes

Signaling
Contact

POWER LED

not lit

-

Power supply failed or turned off

-

Module defective

-

Ribbon band cable not plugged in when assem-
bling the module

Always si-
gnals

POWER LED

lit green

TX LED

not lit

RX LED

not lit

-

Interruption on one or more cores of the RS 485
LAN cable

-

Reversed connection of core A and B of the RS
485 LAN cable

-

Connected PROFIBUS master defective (not sen-
ding)

-

PROFIBUS node is not attached or attached
PROFIBUS node is not turned on

-

No partner station detected with attached PROFI-
BUS master

POWER LED

lit green

TX LED

not lit

RX LED

lit yellow

-

Interruption on one or more cores of the RS 485
LAN cable

-

Reversed connection of core A and B of the RS
485 LAN cable

-

Attached PROFIBUS slave defective (not sen-
ding)

-

PROFIBUS slave is not attached or attached
PROFIBUS slave is not turned on

-

PROFIBUS slave node not correctly addressed
and therefore not responding

POWER LED

lit green

TX LED

lit orange,

RX LED

not lit

-

No acknowledgment pulse received, partner sta-
tion not responding

Signals when
configured
(acknowledg-
ment pulse)

Advertising