Siemens SIMATIC NET PROFIBUS User Manual

Page 141

Advertising
background image

Passive Components for RS-485 Networks

4-43

PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000

5. Screw the green and red cores tight in the screw terminal.

LAN cable attachment for
first and last station on the
bus

1

LAN cable attachment for all
further stations
on the bus

1

: The LAN cable must always be connected up on the left-hand side.

A B

A B

A B

A B

Switch = “ON”
(terminating resistor
activated)

Switch = “OFF”
(terminating resistor
deactivated)

Cable shield must make
good contact with the metal
part.

Cable shield must make
good contact with the metal
part.

Figure 4-23

Connecting the LAN Cable to Bus Connector (6ES7 972-0B.40 ...)

6. Fasten the cover again with the screws.

Note

Stranded cores must only be used in screw terminals with wire-end ferrules fitted
(0.25 mm

2

complying with DIN 46228). Use only wire-end ferrules made of

materials with permanently stable contact properties, for example copper with a
tin-plated surface (not aluminum).

Advertising