4 Setting Up

4.3 Setting compatibility, operating mode and transmitting power

4.3 Setting compatibility, operating mode and transmitting power

Please note:

The OLM must be switched off when changing the operating mode.
You can switch off the OLM by, e.g., unplugging the 5-pin terminal block.

4.3.1 Setting the compatibility

The DIL switch S7 is used to switch the functional compatibility to devices of the preceding generation (SINEC L2FO
OLM/P3, -P4, -S3, -S4, S3-1300 and -S4-1300) either off or on. Default setting at S7 is Position 0 (compatibility is
switched off).

DIL switch S7 (compatibility) in Position 0:
compatibility
to SINEC L2FO OLM/P3, -P4, -S3, -S4, -S3-1300, -S4-1300 switched off

DIL switch S7 (compatibility) in Position 1:
compatibility
to SINEC L2FO OLM/P3, -P4, -S3, -S4, -S3-1300, -S4-1300 switched on

The functional compatibility to SINEC L2 Optical Link Modules of the preceding generation SINEC L2FO OLM/P3,
OLM/P4, OLM/S3, OLM/S4, OLM/S3-1300 and OLM/S4-1300 is switched on with the DIL switch S7=1.
This operating mode is required when operating this module together with new devices.
Only turn switch S7 to Position 1 if the PROFIBUS OLM is being used as a spare or expansion device in existing
networks in conjunction with OLMs of the preceding generation, and a direct optical connection is to be made.

The following illustrations show the switch assignment of the OLM at S7=1 for

Further information about adjusting the S7 in Position 1
can be found in the ”Description and Operating
Instructions SINEC L2 Optical Link Module OLM/P …,
OLM/S …“ for this SINEC L2 OLM.

SINEC L2FO
OLM/S3; OLM/S4;
OLM/S3-1300; OLM/S4-1300

OLM/S3, OLM/S3-1300:
S2 reserved

OLM/S3, OLM/S4,
OLM/S3-1300 und
OLM/S4-1300:

SINEC L2FO
OLM/P3; OLM/P4

OLM/P3 und OLM/P4:

OLM/P3: S6 reserved

S7 = 1 Compatibility Mode ON

S0

Reserved

S3,S4

Reserved

S1

Mode

Monitor

0

Line/Ring

On

1

Line

Off

0

Off

1

On

S2

Redundancy

S7 = 1 Compatibility Mode ON

S0

Reserved

S1

Mode

Monitor

0

Line/Ring

On

1

Line

Off

0

Off

1

On

S2

Redundancy

S5

Output Power CH3

0

Standard

1

High

0

Standard

1

High

S6

Output Power CH4

S3

Distance

0

Extended

1

Standard

S4,S5,S6

Reserved

0

1

S 6

S 7

S 1

S 2

S 4

S 5

S 3

S 0

0

1

S 6

S 7

S 1

S 2

S 4

S 5

S 3

S 0