Passive Components for RS-485 Networks

4-46

PROFIBUS Networks SIMATIC NET

6GK1970-5CA20-0AA1 Release 2 05/2000

4.6

Plugging the Bus Connector into the Module

Fitting the Bus Connector

To fit the bus connector, follow the steps outlined below:

1. Plug the bus connector into the module.

2. Screw the bus connector to the module.

3. If the bus connector is located at the start or end of a segment, you must

activate the terminating resistor (switch setting ON”) (see Figure 4-26).

It is not possible to activate the terminating resistor on the bus connector
6ES7 972-0BA30-0XA0.

Note

Remember the following:

S

By activating the terminating resistor, the outgoing LAN cable is
disconnected from the incoming LAN cable.

S

Stations equipped with a terminating resistor must always be
supplied with voltage when the network starts up and during
operation.

Terminating
resistor activated

Terminating resistor
not activated

on

off

on

off

Figure 4-26

Bus Connector (6ES7 972-0B.11-...): Terminating Resistor Activated and
deactivated

Removing the Bus Connector

If the LAN cable is connected through, you can remove the bus connector from
the PROFIBUS-DP interface at any time without interrupting data traffic on the
bus.