Electrical Connection

Installation Guide

SMC50A_60A-IEN073320

Page 33

Design Notes

Check the following points below:

Step

Test

1

Do all the strings have the same number of series-connected modules?

2

How high is the maximum reverse current in a defective string at nominal
conditions?
Example: generator with 4 strings of modules at 5 A short-circuit current
The maximum reverse current is 3 x 5 A = 15 A.

3

Are the modules suitable for such a reverse current?

4

If not: Have appropriate measures been taken in order to avoid these
currents (e.g. string fuse in each string)?

5

Are the plug connectors of the modules and the inverter suitable for such a
reverse current?

6

Is the string wiring suitable for such a reverse current?