SMC Networks Sunny Mini Central SMC 5000A User Manual

Page 83

Advertising
background image

SMA

Technologie AG

Technical Data

Installation Guide

SMC50A_60A-IEN073320

Page 83

Control

Current regulation switching. If the operating parameter "Control" is
set to "Auto", the inverter automatically chooses the optimal type of
current regulation. If the operating parameter "Control" is set to
"Grid", the inverter regulates on the grid side. If set to "Bridge", the
inverter regulates on the bridge side. This setting can be a corrective
measure in the event of difficult grid characteristics. Discuss the
alteration of this parameter with the SMA Serviceline.

Default

Used for setting country-specific information.

GER/VDE0126-1-1: country-specific parameter settings for
Germany in accordance with DIN VDE 0126-1-1

SP/RD1663: country-specific parameter settings
for Spain

AUS/AS4777: country-specific parameter settings
for Australia

IT/DK5950: country-specific parameter settings
for Italy

GB/G83: country-specific parameter settings
for Great Britain

Other: parameter settings can be defined here for countries
where no predefined setting exists.

Trimmed: If country-specific parameters have been changed,
"trimmed" is shown on the display.

Off_Grid: Setting for inverters which are operated in a stand-
alone grid. More detailed information can be found in the
Sunny Island manual.

dFac-Max

Maximum "grid frequency change" before the grid monitoring
system disconnects the device from the grid.

dZac-Max

Maximum "grid impedance change" before the grid monitoring
system disconnects the device from the grid.

E_Total

Total energy yield of the inverter. This change may be necessary
when you exchange your Sunny Mini Central and want to use the
data from the old device.

Fac-delta-

Maximum frequency, above (Fac-delta+) and below (Fac-delta-) the
grid frequency, before the grid monitoring system disconnects the
device from the grid.

Fac-delta+

Fac-Limit delta

For setting the frequency-dependent output derating in the operating
mode "Off Grid". Further information on this topic can be found in
the Sunny Island operating manual.

Name

Explanation

Advertising