Grid Connection Data

Nominal output power

P

ACnom

5000 W

Peak output power

P

AC, max

5500 W

Nominal output current

I

ACnom

21.7 A

Max. output current

I

AC, max

26 A

Harmonic distortion of output current
(at KUgrid < 2 %,
PAC > 0.5 PACnom)

K

IAC

< 4 %

Short-circuit proofing

current control

Nominal operational voltage

U

ACnom

230 V

Operating range, grid voltage
(complying with
DIN VDE 0126-1-1)

U

AC

198 ... 253 V / 260 V

a

Voltage range
(extended operating range)

U

AC

180 V - 265 V

Nominal operating frequency

f

ACnom

50 Hz / 60 Hz

Operating range, grid frequency
(complying with
DIN VDE 0126-1-1)

f

AC

47.5 Hz - 50.2 Hz

Frequency range
(extended operating range)

f

AC

50 Hz: 45.5 Hz - 54.5 Hz
60 Hz: 55.5 Hz - 64.5 Hz

All-pole isolator on grid side

automatic disconnection device
(SMA grid guard 2)

Power factor

cos phi 1

Overvoltage category

III

Test voltage (50 Hz)

2 kV

Test surge voltage

4 kV (serial interface: 6 kV)

Operating consumption in night
mode

0.25 W