14.4.2 Parameter Settings for Germany

Grayed out parameters are only displayed in installer mode. The table below contains
the parameters that are applicable in Germany.

Name

Short
descr.

Value range

Default setting

SMC 5000A

SMC 6000A

ACVtgRPro

V

230 ... 300

253

253

AntiIsland-
Ampl *

grd

0 ... 10

0

0

AntiIsland-
Freq *

mHz

0.1 ... 2000

500

500

Betriebsart

MPP, Ikonst, Stop,
Turbine Mode,
U-konst, Off_grid

MPP

MPP

Control

Auto, Grid,
Bridge

Auto

Auto

Default *

GER/VDE0126-1-1,
GB/G83,
AUS/AS4777,
USA/UL1741,
IT/DK5950,
Off_Grid,
SP/RD1663,
Other, trimmed

GER/VDE0126-1-1 GER/VDE0126-1-1

dFac-MAX *

Hz/s

0.1 ... 4.0

4

4

dZac-MAX *

mOhm 0.35 ... 20000

685

670

E_Total

kWh

0 ... 200000

0

0

Fac-delta- *

Hz

0.1 ... 4.5

2.45

2.45

Fac-delta+ *

Hz

0.1 ... 4.5

0.19

0.19

Fac-Limit delta Hz

0 ... 5

2

2

Fac-Start delta Hz

0 ... 5

1

1

Fan test

0 ... 1

0

0

h_Total

h

0 ... 200000

0

0

Inst.-Code

I-NiTest *

mA

0 ... 25000

16000

16000