4. Clear Text Display Module & System Parameters

English

© STÖBER plc 1997

17

05.02.01

Parameter Function

Range

[Default]

Description / Notes

P007

Keypad control

0 - 1

[0]

0 = The RUN, REVERSE and JOG buttons are disabled. Control is

via digital inputs (see parameters P051 - P053).

and

may

still be used to control frequency provided that P124 = 1 and a
digital input has not been selected to perform this function.

1 = OPm2 buttons are enabled (can be individually disabled

depending on the setting of parameters P121 - P124). The
digital inputs for RUN, JOG and

/

are disabled.

P009

••••

Parameter protection setting

0 - 3

[0]

Determines which parameters can be adjusted:

0 = Only parameters from P001 to P009 can be read/set.
1 = Parameters from P001 to P009 can be set and all other

parameters can only be read.

2 = All parameters can be read/set but P009 automatically

resets to 0 when power is removed.

3 = All parameters can be read/set.

P011

Frequency setpoint memory

0 - 1

[0]

0 = Disabled
1 = Enabled. The setpoint alterations made with the

/

buttons or

digital inputs are stored even when power has been removed
from the inverter.

P012

••••

Minimum motor frequency (Hz)

0 - 120.00

[0.00]

Sets the minimum motor frequency (must be less than the value of
P013).

P013

••••

Maximum motor frequency (Hz)

0 - 120.00

[50.00]

Sets the maximum motor frequency.

P014

••••

Skip frequency 1 (Hz)

0 - 120.00

[0.00]

A skip frequency can be set with this parameter to avoid the effects of
mechanical resonance. Frequencies within +/-(value of P019) of this
setting are suppressed. Stationary operation is not possible within the
suppressed frequency range - the range is just passed through.

P015

••••

Automatic restart after mains
failure.

0 - 1

[0]

Setting this parameter to ‘1’ enables the inverter to restart
automatically after a mains break or ‘brownout’, provided the run/stop
switch is still closed or the link is fitted, P007 = 0 and P910 = 0, 2 or 4.

0 = Disabled
1 = Automatic restart

P016

••••

Start on the fly

0 - 2

[0]

Allows the inverter to start onto a spinning motor.
Under normal circumstances the inverter runs the motor up from 0 Hz.
However, if the motor is still spinning or is being driven by the load, it will
undergo braking before running back up to the setpoint - this can cause an
overvoltage trip. By using a flying restart, the inverter ramps up the output
voltage at the setpoint for the period defined by P020.

0 = Normal restart
1 = Flying restart after power up, fault or OFF2 ( if P018 = 1).
2 = Flying restart every time (useful in circumstances where the

motor can be driven by the load).

P017

••••

Smoothing type

1 - 2

[1]

1 = Continuous smoothing (as defined by P004).
2 = Discontinuous smoothing. This provides a fast unsmoothed

response to STOP commands and requests to reduce frequency.

Note: P004 must be set to a value > 0.0 for this parameter to have

any effect.