4. Clear Text Display Module & System Parameters

© STÖBER plc 1998

05.02.01

20

Parameter Function

Range

[Default]

Description / Notes

P051

Selection control function, DIN1

0 - 19

(terminal 5), fixed frequency 3

[1]

or binary fixed frequency bit 0.

P052

Selection control function, DIN2

0 - 19

(terminal 6), fixed frequency 2.

[2]

or binary fixed frequency bit 1.

P053

Selection control function, DIN3

0 - 19

(terminal 7), fixed frequency 1

[10]

or binary fixed frequency bit 2.

Value

0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

Function of P051 to P053

Input disabled

ON right

ON left

Reverse

OFF2 *

OFF3 *

Fixed frequencies 1 - 3

Jog right

Jog left

Remote operation

Fault code reset

Increase frequency **

Decrease frequency **

Disable analogue input

(setpoint is 0.0 Hz)

Disable the ability to change

parameters

Enable dc brake

Do not use

Binary fixed frequency control

(fixed frequencies 1 - 7)

As 6, but input high will also

request RUN *

External trip/PTC

Function,

low state

-

Off

Off

Normal

OFF2

OFF3

Off

Off

Off

Local

Off

Off

Off

Analogue

on

‘P’ Enabled

Off

-

Off

Off

Yes (F012)

Function,

high state

-

On right

On left

Reverse

On

On

On

Jog right

Jog left

Remote

Reset on

rising edge

Increase

Decrease

Analogue

disabled

‘P’ Disabled

Brake on

-

On

On

No

* See section 3.7.

** Only effective when P007 = 0.

Binary Coded Fixed Frequency Mapping

(P051, P052, P053 = 17)

DIN3 (P053) DIN2 (P052) DIN1 (P051)

STOP

0

0

0

RUN to FF1 (P041)

0

0

1

RUN to FF2 (P042)

0

1

0

RUN to FF3 (P043)

0

1

1

RUN to FF4 (P044)

1

0

0

RUN to FF5 (P046)

1

0

1

RUN to FF6 (P047)

1

1

0

RUN to FF7 (P048)

1

1

1

P056

Digital input debounce time

0 - 2

[0]

Use a fast response time only when a ‘clean’ input signal

is used, e.g. from a PLC. Use a slow response time to

allow filtering of the signal if a noisy input (e.g. a switch) is

used.

0 = 12.5 ms

1 = 7.5 ms

2 = 2.5 ms

P058

● RUN command delay (seconds)

0.0 - 650.0

[0.0]

Sets a time delay before the RUN command takes effect.

This parameter affects run commands from all sources

except the RUN button on the OPm2 (this activates the

drive immediately)..