P027, P028, P029 – Siemens Stober CombiDrive CM400/3 User Manual

Page 21: P031, P032, P035, P041, P042, P043, P044

Advertising
background image

4. Clear Text Display Module & System Parameters

English

© STÖBER plc 1997

19

05.02.01

Parameter Function

Range

[Default]

Description / Notes

P027

••••

Skip frequency 2 (Hz)

0 - 120.00

[0.00]

See P014.

P028

••••

Skip frequency 3 (Hz)

0 - 120.00

[0.00]

See P014.

P029

••••

Skip frequency 4 (Hz)

0 - 120.00

[0.00]

See P014.

P031

••••

Jog frequency right (Hz)

0 - 120.00

[5.00]

Jogging is used to advance the motor by small amounts. It is

controlled via the JOG button or with a non-latching switch on one of

the digital inputs (P051 to P053).
If jog right is enabled (DINn = 7), this parameter controls the frequency at

which the inverter will run when the switch is closed. Unlike other setpoints, it

can be set lower than the minimum frequency.

P032

••••

Jog frequency left (Hz)

0 - 120.00

[5.00]

If jog left is enabled (DINn = 8), this parameter controls the frequency at which

the inverter will run when the switch is closed. Unlike other setpoints, it can be

set lower than the minimum frequency.

P035

Reverse motor direction

0 - 1

[0]

0 = Normal direction control.

1 = Direction control is reversed.

P041

••••

Fixed frequency 1 (Hz)

0 - 120.00

[5.00]

Valid if P006 = 2 and P053 = 6 or 18 or P051 = P052 = P053 = 17.

P042

••••

Fixed frequency 2 (Hz)

0 - 120.00

[10.00]

Valid if P006 = 2 and P052 = 6 or 18 or P051 = P052 = P053 = 17.

P043

••••

Fixed frequency 3 (Hz)

0 - 120.00

[15.00]

Valid if P006 = 2 and P051 = 6 or 18 or P051 = P052 = P053 = 17.

P044

••••

Fixed frequency 4 (Hz)

0 - 120.00

[20.00]

Valid if P006 = 2 and P051 = P052 = P053 = 17.

P045

Inversion fixed setpoints for

fixed frequencies 1 - 4

0 - 7

[0]

Sets the direction of rotation for the fixed frequency:

FF 1

FF 2

FF 3

FF 4

P045 = 0

P045 = 1

P045 = 2

P045 = 3

P045 = 4

P045 = 5

P045 = 6

P045 = 7

⇒ Fixed setpoints not inverted.

Fixed setpoints inverted.

P046

••••

Fixed frequency 5 (Hz)

0 - 120.00

[25.00]

Valid if P006 = 2 and P051 = P052 = P053 = 17.

P047

••••

Fixed frequency 6 (Hz)

0 - 120.00

[30.00]

Valid if P006 = 2 and P051 = P052 = P053 = 17.

P048

••••

Fixed frequency 7 (Hz)

0 - 120.00

[35.00]

Valid if P006 = 2 and P051 = P052 = P053 = 17.

P050

Inversion fixed setpoints for

fixed frequencies 5 - 7

0 - 7

[0]

Sets the direction of rotation for the fixed frequency:

FF 5

FF 6

FF 7

P050 = 0

P050 = 1

P050 = 2

P050 = 3

P050 = 4

P050 = 5

P050 = 6 or 7

⇒ Fixed setpoints not inverted.

Fixed setpoints inverted.