4. Clear Text Display Module & System Parameters

English

© STÖBER plc 1997

21

05.02.01

Parameter Function

Range

[Default]

Description / Notes

P061

Selection relay output RL1

0 - 13

[6]

Value Relay function

Active

4

0

No function assigned (relay not active)

Low

1

Inverter is running

High

2

Inverter frequency 0.0 Hz

Low

3

Motor run right has been selected

High

4

External brake on (see parameters P063/P064)

1

Low

5

Inverter frequency less than or equal to minimum

frequency

Low

6

Fault indication

2

Low

7

Inverter frequency greater than or equal to setpoint

High

8

Warning active

3

Low

9

Output current greater than or equal to P065

High

10

Motor current limit (warning)

3

Low

11

Motor over temperature (warning)

3

Low

12

Closed loop motor LOW speed limit

High

13

Closed loop motor HIGH speed limit

High

1

External brake requires 24 V (max.) dc slave relay.

2

Inverter switches off (see parameter P930 and section 5).

3

Inverter does not switch off (see parameter P931).

4

‘Active low’ = relay OPEN. ‘Active high’ = relay CLOSED.

P062

Electro-mechanical brake option
control

0 - 4

[0]

This enables or disables the electro-mechanical brake option.
Operation is the same as for P061 = 4, except that the brake control

voltage is supplied directly.

0 =

Disabled

1 - 3 = Do not use

4 =

Enabled

P063

External brake release delay
(seconds)

0 - 20.0

[1.0]

Only effective if the relay output is set to control an external brake (P061

= 4) or the electro-mechanical brake option is used (P062 = 4). In this

case when the inverter is switched on, it will run at the minimum

frequency for the time set by this parameter before releasing the brake

control relay and ramping up (see illustration in P064).

P064

External brake stopping time
(seconds)

0 - 20.0

[1.0]

As P063, only effective if the relay output is set to control an external
brake (P061 = 4) or the electro-mechanical brake option is used (P062 =
4). This defines the period for which the inverter continues to run at
the minimum frequency after ramping down and while the external
brake is applied.

Notes: (1)

Settings for P063 and P064 should be slightly longer

than the actual time taken for the external brake to

apply and release respectively.

(2)

Setting P063 or P064 to too high a value, especially

with P012 set to a high value, can cause an

overcurrent warning or trip as the inverter attempts to

move a locked motor shaft.

ON

OFF

t

P063

A

t

P064

A

f

f

min

B

t

A = Brake applied
B = Brake removed