Parameter Function

Range

[Default]

Description / Notes

P123

Enable/disable JOG button

0 - 1

[1]

0 = JOG button disabled.
1 = JOG button enabled (only possible if P007 = 1).

P124

Enable/disable

and

buttons

0 - 1

[1]

0 =

and

buttons disabled.

1 =

and

buttons enabled (only possible if P007 = 1).

Note:

This applies for frequency adjustment only. The buttons can
still be used to change parameter values.

P125

Reverse direction inhibit

0 - 1

[1]

0 = Reverse direction disabled. Inhibits reverse commands from

ALL sources (reverse RUN commands result in forward rotation)

1 = Normal operation (FORWARD/REVERSE operation allowed)

P131

Frequency setpoint (Hz)

0.00 -120.00

[-]

P132

Motor current (A)

0.0 - 99.9

[-]

P134

DC link voltage (V)

0 - 1000

[-]

P135

Motor RPM

0 - 40000

[-]

P137

Output voltage (V)

0 - 1000

[-]

P140

Most recent fault code

0 - 9999

[-]

The last recorded fault code (see section 5) is stored in this
parameter. It is cleared when the inverter is reset.
This is a copy of the code stored in P930.

P141

Most recent fault code -1

0 - 9999

[-]

This parameter stores the last recorded fault code prior to that stored
in P140/P930.

P142

Most recent fault code -2

0 - 9999

[-]

This parameter stores the last recorded fault code prior to that stored
in P141.

P143

Most recent fault code -3

0 - 9999

[-]

This parameter stores the last recorded fault code prior to that stored
in P142.

P151

••••

Green LED function

0 - 5

[4]

0 = Off
1 = On
2 = Fault mode:

On = Tripped
Flashing = Warning

3 = Running mode:On = Motor running

Flashing = Inverter on but motor

stationary
4 = Default mode (see table in section 3.6)
5 = Not used

P152

••••

Yellow LED function

0 - 5

[5]

0 = Off
1 = On
2 = Fault mode:

On = Tripped
Flashing = Warning

3 = Running mode:On = Motor running

Flashing = Inverter on but motor

stationary
4 = Not used
5 = Default mode (see table in section 3.6)

P201

PI closed loop mode

0 - 2

[0]

0 = Normal operation (closed loop control disabled).
1 = Not used
2 = Closed loop control using PI input for transducer feedback.

P202

••••

P gain (%)

0.0 - 999.9

[1.0]

Proportional gain.

Read-only parameters. These are copies of the values selected
by P001 but can be accessed directly via the serial link.